Program 320 – Layered cylinder and charging pump
Only practical with speed control activated!
(Absolute value control: mode „Normal“ and sensor input S1)
Program 320:
Solar pumps
A1
run, if:
•
S1
exceeds the threshold
min1
• and
S1
is greater than
S2
by the difference
diff1
• and
S2
has not exceeded the threshold
max1
.
The three-way valve
A2
switches
upwards,
if:
•
S5
exceeds the threshold
min2
, •
or,
if
S5
falls below
min2
,
S5
is greater than
S4
by the
difference
diff2
• and
S4
has not exceeded the threshold
max2
.
The charging pump
A3
runs, if:
•
S6
exceeds the threshold
min3
• and
S6
is greater than
S2
by the difference
diff3
• and
S2
has not exceeded the threshold
max3
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = (S5 > min2 or S5 > (S4 + diff2)) & S4 < max2
A3 = S6 > (S2 + diff3) & S6 > min3 & S2 < max3
All pr1:
If
S4
has reached the threshold
max2
, the rapid warm-up phase is complet
-
ed and the speed control is blocked, which achieves optimal efficiency.
If control Output A4 is activated, the analogue level for maximum speed will be output. Con
-
trol Output A5 is not affected and continues regulating.
All pr8
(independent charging pump
A3
): charging pump
A3
runs, if:
•
S6
exceeds the threshold
min3
• and
S6
is greater than
S3
by the difference
diff3
• and
S3
has not exceeded the threshold
max3
.
A3 = S6 > (S3 + diff3) & S6 > min3 & S3 < max3
necessary settings:
max1
max2
max3
min1
min2
min3
diff1
diff2
diff3
... limit CYL
S2
... limit CYL
S4
... limit CYL
S2
... activation temp. coll.
S1
... activation temp. HE
S5
... activation temp. boiler
S6
... coll.
S1
- CYL
S2
... HE
S5
- CYL
S4
... boiler
S6
- CYL
S2
à
A1
à
A2
à
A3
à
A1
à
A2
à
A3
à
A1
à
A2
à
A3