TL1 Reference
Retrieve Commands
408
TSG-3800 User’s Guide
12778474-002-2 Revision F – March 2004
Retrieve Frequency Parameter
The Retrieve Frequency Parameter command reports the frequency threshold
settings for the specified input port. The settings for each time period (100, 1000,
and 10000 seconds) are reported on three separate lines for each input port.
If the TSG-3800 successfully receives the command, it returns the COMPLD
message. If the TSG-3800 does not successfully receive the command, it returns
the DENY message.
Retrieve MTIE Parameter
The Retrieve MTIE Parameter command reports the MTIE threshold settings for the
specified input port. The settings for each time period (100, 1000, and 10000
seconds) are reported on three separate lines for each input port.
If the TSG-3800 successfully receives the command, it returns the COMPLD
message. If the TSG-3800 does not successfully receive the command, it returns
the DENY message.
Command Syntax
RTRV-PRMTR-FREQ:[tid]:[aid]:ctag;
Valid aid
INP, INPx, INPx[-y], ALL, <null>
Minimum User Level
2
Response Format
<cr><lf><lf>
M^ctag^COMPLD<cr><lf>
^^^aid:FREQ,lim1,mod1,lim2,mod2,tmper<cr><lf>
where:
lim1 and lim2 are the threshold values
mod1 and mod2 are the alarm mode settings
[Fail|Alarm|Rept| Ignr]
tmper is 100|1000|10000
Example Command
RTRV-PRMTR-FREQ:TSG::ctag;
Example Response
TSG 02-09-10 19:00:19
M 13 COMPLD
^^^TSG:
;
Command Syntax
RTRV-PRMTR-MTIE:[tid]:[aid]:ctag;
Valid aid
INP, INPx, INPx[-y], ALL, <null>