12778474-002-2 Revision F – March 2004
TSG-3800 User’s Guide
75
Installing the TSG-3800
Input/Output Adapter Panels
Mount the panel in the equipment rack by performing the following steps.
1. Position the panel against the equipment rack directly above the associated tie
bar. The cable tie bar and panel requires three rack units (3RU). One rack unit
equals 1.75 inches (4.45 cm).
2. Attach the panel to the equipment rack with four screws and associated
hardware. Ensure that the screws mate with the equipment rack into which you
install the panel.
After installing the panel, secure and protect the cables on the panel. Follow the
instructions below, and use the cable support bar, item number 00112914-000-1,
and the appropriate screws.
Making Output Signal Connections
The telecommunication output signal connectors located on the panel, item number
010-076, are arranged in ten groups of pins that cross-connect with as many as five
connectors, item number 551026-0032. Each group of pins is divided into two pairs
of tip and ring wire connections.
Table 2-12. Input and Output Cross-Connection Signals for Connectors
Groups 2, 4, 6, 8, and 10
Groups 1, 3, 5, 7, and 9
Tip
Pin
Ring
Pin
Tip
Pin
Ring
Pin
T1
26
R1
1
T1
36
R1
11
T2
27
R2
2
T2
37
R2
12
T3
28
R3
3
T3
38
R3
13
T4
29
R4
4
T4
39
R4
14
T5
30
R5
5
T5
40
R5
15
T6
31
R6
6
T6
41
R6
16
T7
32
R7
7
T7
42
R7
17
T8
33
R8
8
T8
43
R8
18
T9
34
R9
9
T9
44
R9
19
T10
35
R10
10
T10
45
R10
20
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com