12778474-002-2 Revision F – March 2004
TSG-3800 User’s Guide 291
Output Modules
Output Fault Analyzer
Input Fault Level
The input signal fault level is preset to 2.0 Vp ±10%, and is not user-selectable.
Signals at or below this level may not be suitable for synchronization of external
equipment.
Installing the Output Fault Analyzer
The Analyzer can be installed and removed while power is applied to the TSG-3800
shelf. How you install the Analyzer depends on whether redundant Output modules
are installed in the shelf.
Non-Redundant Operation
To install the Analyzer:
1. Install the Analyzer into the unoccupied slot associated with the suspect module.
2. Press the Analyzer firmly into the connectors in the backplane of the shelf. It is
not necessary to tighten the captive screws on the front panel of the Analyzer.
3. Continue with the procedure described in
Operating the Output Fault Analyzer
,
on page 291.
Redundant Operation
If a redundant pair of modules is being tested, remove one of the modules before
installing the Analyzer. To install the Analyzer:
1. Remove the Output module with a suspected fault.
2. Insert the Analyzer in the slot, ensuring that it is aligned in the card guides.
3. Press the Analyzer firmly into the connectors in the backplane of the shelf. It is
not necessary to tighten the captive screws on the front panel of the Analyzer.
4. Continue with the procedure described in
Operating the Output Fault Analyzer
,
on page 291.
Operating the Output Fault Analyzer
The Analyzer begins operating as soon as it is installed in the shelf. There are no
settings or configurations to install. The Analyzer may be stored in an inactive slot at
the extreme right of the shelf; in this slot the Analyzer is neither powered nor
operational.
Make the following operational checks after the Analyzer is installed in the
TSG-3800. It is assumed that power is connected to the shelf and that there is an
AMI or CC Output module installed in either slot of a redundant output pair.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com