System Administrator’s Reference
Provisioning Input Reference Signals
336
TSG-3800 User’s Guide
12778474-002-2 Revision F – March 2004
Displaying MTIE Fault Modes
To display the current MTIE fault mode:
MTIE {input} MODE
then press
Enter
where «input» is described in
Table B-3
(default is all inputs)
A typical response from the TSG-3800 is:
TSG->MTIE 1.1 MODE
The MTIE Limit 1 Alarm Mode for Inp1.1 is Alarm
The MTIE Limit 2 Alarm Mode for Inp1.1 is Report
TSG->
Setting MTIE Fault Modes
To set an MTIE fault mode, type:
MTIE «input» MODE [L1|L2] [FAIL|ALARM|REPORT|IGNORE]
then
press
Enter
where «input» is described in
Table B-3
(default is all inputs)
Example
Purpose: Set the MTIE limit 1 to REPORT fault mode.
Command:
MTIE 1.1 MODE L1 REPORT
Display:
TSG->MTIE 1.1 MODE L1 REPORT
«date» «time» «oper» Set Inp1.1 MTIE Alarm Mode l to
Report, was Alarm
TSG->
Displaying MTIE Limits
To display the current MTIE fault limits, type:
MTIE «input» [T100|T1000|T10000] LIMIT
then press
Enter
where «input» is described in
Table B-3
(default is all inputs)
T100, T1000 and T10000 is the time scale in seconds (default
is T100).
A typical response from the TSG-3800 is:
TSG->MTIE 1.1 T1000 LIMIT
The MTIE T1000 Limit 1 Alarm Mode for Inp1.1 is Alarm 432
The MTIE T1000 Limit 2 Alarm Mode for Inp1.1 is Ignore 324
TSG->