31
8.1 OVERVIEW
Alarm settings page sets the condition that will cause an alarm by the PLC. Each button will open a secondary screen
with options for each alarm. Each alarm can either be enabled or disabled. By default, every alarm is disabled, and
editable fields are set to zero.
Note:
Channel 1 and Channel 2 screens contain identical fields and options except where noted.
8.2 LIQUID PRESSURE ALARM SETUP
SECTION 8
ALARM SETTINGS
Item
Description
Ch1 Liq Press Alarm
(toggle)
Enables or disables the liquid pressure alarm.
Min Pressure
(editable)
Sets the minimum pressure allowable before alarming.
Max Pressure
(editable)
Sets the maximum pressure allowable before alarming.
Tolerance Time
(editable)
Sets the maximum allowable time outside the max or min pressure.