29
CH1 APP RATE PID
7.6 REMOTE SETPOINT SETUP
Item
Description
App Rate PID OPEN LOOP
(on/off)
Toggles App Rate PID on/off for specified channel
Flow Rate PV (GPM)
(read only)
Display of the current flow rate.
App Rate SP (mL/SQ FT)
(read only)
Display desired app rate setpoint (mL/sq. ft.).
App Rate PV (mL/SQ FT)
(read only)
Display of the current flow rate.
App Rate CF
(editable)
The app rate correction factor is determined by running the PID in closed loop. It can
be manually adjusted while in open loop.
Kp
(editable)
Proportional value in the PID loop.
Ki
(editable)
Integral value in the PID loop.
Kd
(editable)
Derivative value in the PID loop.
Duty Cycle (%)
(read only)
Displays current duty cycle
LN SPD (FT/MIN)
(read only)
Displays current Line Speed.
PID DLY (mS)
(editable)
Sets the PID delay, or time until the PID begins working to allow for values to ramp
up. (mS)
Graph Scale
(editable)
Change the scale of the graph for readability.
Liq Press PV (PSI)
(read only)
Displays current liquid pressure. (PSI)