Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 163 -
SMA Regelsysteme GmbH
Parameter settings, mandatory in this configuration
The following parameters have to be set for a proper operation of the Sunny Island.
Parameter Unit
Default
Description
Master
Slaves
401_Phase Mode
1Phs_Si
ngle
Device setting
1Phs_
Single
(?)
3Phs_
Slv1L2
/ L3
501_Cbat nom
Ah
350
Nom. battery capacity (C10)
?
X
502_Bat Type
Lead-
Acid
Battery type
?
X
503_Ubat nom
V
60
Nom. battery voltage
60 (?)
X
504_Ubat min
V
51
Min. permissible battery voltage
51 (?)
51 (?)
505_Ubat max
V
84
Max. permissible battery voltage
81 (?)
81 (?)
602_GenSet Type
None
Generator type
BHKW-
Island
None
603_GenSet Interf
None
Generator interface
Eco
Power
X
636_PDump1
W
500
Power of Dumpload 1
500 (?)
X
637_PDump2
W
2000
Power of Dumpload 2
2000
(?)
X
646_PDump3
W
4500
Power of Dumpload 3
4500
(?)
X
701_Man K1
OFF
Operating mode of K1
AUTO
X
702_Man K2
OFF
Operating mode of K2
AUTO
X
706_Man K6
OFF
Operating mode of K6
AUTO
X
710_K1 t2 begin
h
0
Start of special period t2 for K1
?
X
711_K1 t2 end
h
0
End of special period t2 for K1
?
X
712_K1 On t1
N4
Switch-on threshold for K1
?
X
713_K1 Off t1
N1
Switch-off threshold for K1
?
X
714_K1 On t2
N4
Switch-on threshold in special pe-
riod t2 for K1
? X
715_K1 Off t2
N1
Switch-off threshold in special pe-
riod t2 for K1
? X
801_Sunny Boys
Not in-
stalled
Control method for the Sunny
Boys
Fre-
quency
(?)
X
X: don’t care; ?: system-dependent; <value>(?): preferred setting, but system-dependent at last