17 Measured Values Displayed (Overview)
Name Unit
Min.
Max.
Default
Description
“DATSYS” (1-1)
SN:
Serial
number
Vers:
Firmware versions of BFR and DSP
UP:
h
0.0
Operating hour meter
Name Unit
Min.
Max.
Default
Description
“DATALL” (1-2), Passwort-Level: 1
Mode
0
13
0
Current operating state
0: - - - - - - - -
Initialization
1: INIT
Initialization
2: STANDBY
Waiting state
3: SLAVE
Slave mode (three-phase ope
ration)
4: STARTUP
Start
5: RUN_U
Inverter operation (island grid)
6: RUN_UEXT
Generator operated with droop
characteristics
7: RUN_I
Charging operation on grid or
generator
8: GEN_MANU
man. start of generator
detected
9: SYNC_HD
Transfer from RUN_U to
RUN_I
10: SYNC_TK
Transfer from RUN_I to
RUN_U
11: SHUTDOWN Shutdown
12: ERRSHDWN Shutdown due to error
13: Disturbance
Fault state
Batt. Ah In
Ah
0
0
0
Ah into the battery
Batt. Ah Out
Ah
0
0
0
Ah out of the battery
E_Total_In
kWh
0
0
0
Input power AC side
E_Total
kWh
0
0
0
Output power AC-side
Energy Count
h
0
0
0
Run-time of energy counter
h-Total
h
Time since switch-on (“Up-Time“)
Pconv Sum
kW
-320
320
0
Sum of grid active power SI (three phases)
Qconv Sum
kvar
-320
320
0
Sum of grid reactive power SI (three phases)
Sconv Sum
kVA
-320
320
0
Sum of grid apparent power SI (three phases)
Iconv Sum
A
0
640
0
Inverter current (three phases)
Pext Sum
kW
-320
320
0
Sum of generator active power (three phases)