Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 86 -
SMA Regelsysteme GmbH
Fig. 6.1:
Display to enter password
As soon as you have entered the password correctly all settings and val-
ues acquired adaptively up to this point are overwritten with standard va-
lues!
After you have entered the password you will reach a menu where you have to set up
essential, “Master”-oriented parameters for the battery, the connected generator and
the type of island grid to ensure proper operation.
Parameter Default
Description
310_Auto Start
0
Number of autostart attempts (0: autostart off) within one hour.
After one hour the counter will be reset.
Autostart means that approx. 10 sec after a switch-off (due to er-
ror or the like) the Sunny Island restarts.
In addition, the Sunny Island starts automatically after switching
on the DC voltage when the autostart is activated.
ATTENTION:
The Sunny Island will execute this number of autostart attempts
anew in intervals of one hour.
The Sunny Island’s low battery load mode will be deactivated if
this parameter is set to 0!(s. Parameter “535_State Stop T” for
details)
401_Phase
Mode
1Phs_Single
1Phs_Single:
single-phase operation, inverter is the only de-
vice
1Phs_Psingle:
single-phase parallel operation with one battery
per device
(grid and generator not possible!)
1Phs_Mstr2:
single-phase parallel operation with two de-
vices with one single battery pack, device is
master
1Phs_Mstr3:
single-phase parallel operation with three de-
vices with one single battery pack, device is
master
1Phs_Slv2:
single-phase parallel operation with two or
three devices with one single battery pack, de-
vice is slave 2