Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 202 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
625_PldL GenOn
(A)
%
-100 100
0
Switch-on threshold in % of the nominal power at
one phase for the power-related generator start or
the power-related relais (only K5 or K6). If the re-
lays shall be switched in relation to the power, the
parameters “705_Man K5” and/or “706_Man K6”
must be set to “LOAD“.
These settings should only be used for single
phase systems with one Sunny Island per battery.
0: Load-dependent generator activation is inactive
626_PldL GenOff
(A)
%
-100 100
0
Switch-off threshold in % of the nominal power at
one phase for the power-related generator start or
the power-related relais (only K5 or K6). If the re-
lays shall be switched in relation to the power, the
parameters “705_Man K5” and/or “706_Man K6”
must be set to “LOAD“.
These settings should only be used for single
phase systems with one Sunny Island per battery.
0: Load-dependent generator activation is inactive
627_PldS GenOn
(A)
%
-100 100
0
Switch-on threshold in % of the nominal power
based on the cumulative power within the three-
phase system for the power-related generator start
or the power-related relays (only K5 or K6). If the
relays shall be switched in relation to the power,
the parameters “705_Man K5” and/or “706_Man
K6” must be set to “LOAD“.
These settings should be used for systems with
more than one Sunny Island per battery.
0: Load-dependent generator activation is inactive
628_PldS GenOff
(A)
%
-100 100
0
Switch-off threshold in % of the nominal power
based on the cumulative power within the three-
phase system for the power-related generator start
or the power-related relays (only K5 or K6). If the
relays shall be switched in relation to the power,
the parameters “705_Man K5” and/or “706_Man
K6” must be set to “LOAD“.
These settings should be used for systems with
more than one Sunny Island per battery.
0: Load-dependent generator activation is inactive
629_TavgLdLx
(A)
Sec
5
60
10
Averaging time for the power calculation per phase
(see also “625_PldL GenOn” and “626_PldL Gen-
Off”)
630_TavgLdSum
(A)
Min
1
20
1
Averaging time for the calculation of the cumulative
power within the three-phase system (see also
“627_PldS GenOn” and “628_PldS GenOff”)
631_PldLzMin
(A)
%
0
100
60
Lower limit for the charging state, when the Eco-
power CHP will always be started
632_PldLzMax
(A)
%
0
100
85
Upper limit for the charging state, when the Eco-
power CHP will never be started