Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 110 -
SMA Regelsysteme GmbH
8.3 Menu “PARSYS“ (3+3), Parameters System
This menu can only be selected after the installer password (level: 1) has been en-
tered.
Fig. 8.5:
Menu “PARSYS“ (3+3)
In the menu “PARSYS“ (3+3) you can set the parameters that concern the Sunny
Island itself. Essentially these are the settings for communication and thus the inter-
face configuration.
Especially for three-phase systems changes of these settings can lead to
incorrect configuration which the Sunny Island cannot immediately detect
in operation. Therefore changes of interface parameters are only imple-
mented at the next restart of the Sunny Island. Please follow the instruc-
tions indicated at the beginning of Chapter 8.
In this menu the operator can also stipulate the number of autostart attempts to be
made after an error has occurred or the DC voltage has been switched on. If this
value is set to 0 (state in which the inverter is delivered) the Sunny Island does not
start automatically.
By setting the parameter “310_Auto Start” to 0, the low-battery load
mode (see Chapter 16, Parameter “517_BS Tstop“) will be inhibited,
while any positive number will not affect this mode.