Parameter Default
Description
Type 3:
3 contacts Start / Stop, relays K1, K2, K6
EcoPower Ecopower
CHP
(see also Fig. 12.1: Starting phase sequence for different genera-
tor types)
604_GenSet Ctrl
OFF
The Sunny Island reduces its current input in charge operation
(RUN_I) ……
OFF:
... not at all
F_MAINS:
... as a function of generator frequency (see
“407_Fext nom”)
I_GEN:
... as a function of generator current (converter
required, see Chapter 3.4.5)
BOTH:
... as a function of generator frequency (see
“407_Fext nom”) and current (converter re-
quired, see Chapter 3.4.5)
605_GenStRetr
3
Max. number of attempts to start the generator, before the state
“Fail Locked“ is reached (see also parameter 618). After the
minimum run-time of the generator has expired, the counter will
be reset.
606_CurTrfRatio
5 A/5A
Current transformer ratio (in A per 5 A) for measurement of gen-
erator current
607_Igen max
0 A
Max. generator current (per phase),
only applies if “604_GenSet Ctrl” is set accordingly
645_RevPower
-0,5 kW
Generator reverse power protection:
If the power delivered by the generator falls below this value, the
generator will be disconnected
701_Man K1
OFF
Operating mode of relay K1
OFF:
Switch relay K1 off
ON:
Switch relay K1 on
AUTO:
Sunny Island automatically controls relay K1.
702_Man K2
OFF
Operating mode of relay K2 (for details see 701)
703_Man K3
OFF
Operating mode of relay K3 (for details see 701)
704_Man K4
OFF
Operating mode of relay K4 (for details see 701)