Parameter settings, mandatory in this configuration
The following parameters have to be set for a proper operation of the Sunny Island.
Parameter Unit
Default
Description
Master
Slaves
401_Phase Mode
1Phs_Si
ngle
Device setting
1Phs_
Single
(?)
3Phs_
Slv1L2
/ L3
501_Cbat nom
Ah
350
Nom. battery capacity (C10)
?
X
502_Bat Type
Lead-
Acid
Battery type
?
X
503_Ubat nom
V
60
Nom. battery voltage
60 (?)
X
504_Ubat min
V
51
Min. permissible battery voltage
51 (?)
51 (?)
505_Ubat max
V
84
Max. permissible battery voltage
81 (?)
81 (?)
602_GenSet Type
None
Generator type
fast
Mains
(?)
X
703_Man K3
OFF
Operation mode of K3
AUTO
AUTO
704_Man K4
OFF
Operation mode of K4
AUTO
X
801_Sunny Boys
Not in-
stalled
Control method for the Sunny
Boys
Fre-
quency
Not In-
stalled
X: don’t care; ?: system-dependent; <value>(?): preferred setting, but system-dependent at last
Parameter settings, recommended for this configuration
The proper settings of the following parameters should be checked. In general, the
system should function well with the default values, but minor optimizations might be
advisable.
Parameter Unit
Default
Description
Master
Slaves
310_Auto Start
0
Number of autostart attempts
3 (?)
X
506_acid density
kg/l
1,24
Nom. acid density acc. to manufac-
turer
1,24 (?)
X
509_Tbat max
°C
40
Max. battery temperature permissi-
ble
40 (?)
X
X: don’t care; ?: system-dependent; <value>(?): preferred setting, but system-dependent at last