A.6
Output configuration
Pulse output can be configured as volume pulse, alarm or call-up. Default factory setting is
with output A enabled for forward flow and output B for alarm output.
Output configuration in Flow Tool
Select "I/O and Com.Setup". The software window shows the parameters for output
configuration. Each parameter has its own guideline for selecting the correct parameter setting.
To see how the outputs work, please see "Output characteristics" (Page 96).
A.7
Default display information and accessible display menus
Parameter 131 defines default display information with selection between
● Totalizer 1 (Index 1)
● Totalizer 2 (Index 2)
● Flow rate (Index 3, updated with selected measuring frequency)
● Fault codes (Index 4)
● Customer totalizer (Index 5 - resettable)
Default information is shown after power-up as well as after no key operation for 10 minutes.
Parameter 130 defines accessible display menus with selection of one or more of the following
menus:
● Operator menu
● Meter info menu
● Service menu
● Data logger menu
Flow Tool
A.7 Default display information and accessible display menus
SITRANS MAG 8000
Operating Instructions, 11/2018, A5E03071515-AE
125