10.8
FM Fire Service applications (MAG 8000 and MAG 8000 CT)
Devices ordered with Z-option P20, P21 or P22 are FM Fire Service approved for automatic
fire protection systems according to the Fire Service Meters Standard, Class Number 1044.
The approval is applicable for the sizes DN 50, DN 80, DN 100, DN 150, DN 200, DN 250,
and DN 300 (2", 3", 4", 6", 8", 10", and 12") with ANSI B16.5 Class 150 flanges.
FM-Fire Service verification tolerances
1.5 %
Q
max
Q
min
±E%
)0
10.9
MAG 8000 CT (7ME6820) (Revenue program) water meter type
approval
MAG 8000 CT program is type-approved according to international water meter standard OIML
R49. The Custody Transfer program is approved as Class I and Class II, for the sensor program
from DN 50 to DN 300, at different Q3 and Q3/Q1.
Q2/Q1 = 1.6 and follows standard OIML R49 specification.
&O,&O,, 2,0/5&ODVV,&ODVV,,
OIML R49 specification for Class I
Size
50 (2")
65 (2½") 80 (3")
100 (4")
125 (5")
150 (6")
200 (8")
250 (10") 300 (12")
"R" Q
3
/Q1
250
250
250
250
250
250
250
250
125
Q4 [m
3
/h]
78.75
125
200
312.5
500
787.5
1250
2000
2000
Q3 [m
3
/h]
63
100
160
250
400
630
1000
1600
1600
Q2 [m
3
/h]
0.4
0.64
1
1.6
2.5
4
6.4
10
20.48
Q1 [m
3
/h]
0.25
0.4
0.63
1
1.6
2.5
4
6.4
12.8
OIML R49 specification for Class II
Size
50 (2")
65 (2½") 80 (3")
100 (4")
125 (5")
150 (6")
200 (8")
250 (10") 300 (12")
"R" Q
3
/Q1
400
400
400
400
400
400
400
400
200
Q4 [m
3
/h]
78.75
125
200
312.5
500
787.5
1250
2000
2000
Q3 [m
3
/h]
63
100
160
250
400
630
1000
1600
1600
Technical data
10.9 MAG 8000 CT (7ME6820) (Revenue program) water meter type approval
SITRANS MAG 8000
Operating Instructions, 11/2018, A5E03071515-AE
103