Appendix
A.7 Settings
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
689
1542
ϕ
load (Ø-E)
Dis. General
20 .. 60 °
45 °
PHI load, maximum Load Angle
(ph-e)
1542
ϕ
load
Dis. General
20 .. 60 °
45 °
PHI load, maximum Load Angle
1543
R load (Ø-Ø)
Dis. General
1A
0.100 .. 600.000
Ω
;
∞
∞ Ω
R load, minimum Load Imped-
ance (ph-ph)
5A
0.020 .. 120.000
Ω
;
∞
∞ Ω
1544
ϕ
load (Ø-Ø)
Dis. General
20 .. 60 °
45 °
PHI load, maximum Load Angle
(ph-ph)
1601
Op. mode Z1
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
Forward
Operating mode Z1
1602
R(Z1) Ø-Ø
Dis. Quadril.
1A
0.050 .. 600.000
Ω
1.250
Ω
R(Z1), Resistance for ph-ph-
faults
5A
0.010 .. 120.000
Ω
0.250
Ω
1603
X(Z1)
Dis. Quadril.
1A
0.050 .. 600.000
Ω
2.500
Ω
X(Z1), Reactance
5A
0.010 .. 120.000
Ω
0.500
Ω
1604
RE(Z1) Ø-E
Dis. Quadril.
1A
0.050 .. 600.000
Ω
2.500
Ω
RE(Z1), Resistance for ph-e
faults
5A
0.010 .. 120.000
Ω
0.500
Ω
1605
T1-1phase
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec;
∞
0.00 sec
T1-1phase, delay for single
phase faults
1606
T1-multi-phase
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec;
∞
0.00 sec
T1multi-ph, delay for multi phase
faults
1607
Zone Reduction
Dis. Quadril.
0 .. 45 °
0 °
Zone Reduction Angle (load
compensation)
1608
Iph>(Z1)
Dis. Quadril.
Dis. MHO
1A
0.05 .. 20.00 A
0.20 A
Minimum current for Z1 only
Iph>(Z1)
5A
0.25 .. 100.00 A
1.00 A
1611
Op. mode Z2
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
Forward
Operating mode Z2
1612
R(Z2) Ø-Ø
Dis. Quadril.
1A
0.050 .. 600.000
Ω
2.500
Ω
R(Z2), Resistance for ph-ph-
faults
5A
0.010 .. 120.000
Ω
0.500
Ω
1613
X(Z2)
Dis. Quadril.
1A
0.050 .. 600.000
Ω
5.000
Ω
X(Z2), Reactance
5A
0.010 .. 120.000
Ω
1.000
Ω
1614
RE(Z2) Ø-E
Dis. Quadril.
1A
0.050 .. 600.000
Ω
5.000
Ω
RE(Z2), Resistance for ph-e
faults
5A
0.010 .. 120.000
Ω
1.000
Ω
1615
T2-1phase
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec;
∞
0.30 sec
T2-1phase, delay for single
phase faults
1616
T2-multi-phase
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec;
∞
0.30 sec
T2multi-ph, delay for multi phase
faults
1617A
Trip 1pole Z2
Dis. General
Dis. Quadril.
Dis. MHO
NO
YES
NO
Single pole trip for faults in Z2
1621
Op. mode Z3
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
Reverse
Operating mode Z3
1622
R(Z3) Ø-Ø
Dis. Quadril.
1A
0.050 .. 600.000
Ω
5.000
Ω
R(Z3), Resistance for ph-ph-
faults
5A
0.010 .. 120.000
Ω
1.000
Ω
1623
X(Z3)
Dis. Quadril.
1A
0.050 .. 600.000
Ω
10.000
Ω
X(Z3), Reactance
5A
0.010 .. 120.000
Ω
2.000
Ω
1624
RE(Z3) Ø-E
Dis. Quadril.
1A
0.050 .. 600.000
Ω
10.000
Ω
RE(Z3), Resistance for ph-e
faults
5A
0.010 .. 120.000
Ω
2.000
Ω
1625
T3 DELAY
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec;
∞
0.60 sec
T3 delay
1631
Op. mode Z4
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
Non-Directional
Operating mode Z4
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments