Functions
2.22 Circuit Breaker Failure Protection
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
405
Address
3913
T2StartCriteria
is used to set whether the delay time
T2
will be started after expiry of T1
(
T2StartCriteria
=
With exp. of T1
) or simultaneously with it (
T2StartCriteria
=
Parallel
withT1
). The time
T2
can also be initiated via a separate binary input 1424
„>BF STARTonlyT2“
.
Figure 2-194
Logic diagram of the two-stage breaker failure protection