Functions
2.1 General
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
71
6028
S2: center ph.
unknown/sym.
Phase 1
Phase 2
Phase 3
unknown/sym.
S2: center phase
6029
S2: XE/XL
-0.33 .. 10.00
1.00
S2: Zero seq. compensat-
ing factor XE/XL
6030
S2: RE/RL
-0.33 .. 10.00
1.00
S2: Zero seq. compensat-
ing factor RE/RL
6031
S2: K0
0.000 .. 4.000
1.000
S2: Zero seq. compensat-
ing factor K0
6032
S2: angle K0
-180.00 .. 180.00 °
0.00 °
S2: Zero seq. compensat-
ing angle of K0
6041
S3: Line angle
30 .. 89 °
85 °
S3: Line angle
6042
S3: x'
1A
0.0050 .. 9.5000
Ω
/km
0.1500
Ω
/km
S3: feeder reactance per
km: x'
5A
0.0010 .. 1.9000
Ω
/km
0.0300
Ω
/km
6042
S3: x'
1A
0.0050 .. 15.0000
Ω
/mi
0.2420
Ω
/mi
S3: feeder reactance per
mile: x'
5A
0.0010 .. 3.0000
Ω
/mi
0.0484
Ω
/mi
6043
S3: c'
1A
0.000 .. 100.000 µF/km
0.010 µF/km
S3: feeder capacitance c'
in µF/km
5A
0.000 .. 500.000 µF/km
0.050 µF/km
6043
S3: c'
1A
0.000 .. 160.000 µF/mi
0.016 µF/mi
S3: feeder capacitance c'
in µF/mile
5A
0.000 .. 800.000 µF/mi
0.080 µF/mi
6044
S3: Line length
0.1 .. 1000.0 km
100.0 km
S3: Line length in kilome-
ter
6044
S3: line length
0.1 .. 650.0 Miles
62.1 Miles
S3: line length in miles
6048
S3: center ph.
unknown/sym.
Phase 1
Phase 2
Phase 3
unknown/sym.
S3: center phase
6049
S3: XE/XL
-0.33 .. 10.00
1.00
S3: Zero seq. compensat-
ing factor XE/XL
6050
S3: RE/RL
-0.33 .. 10.00
1.00
S3: Zero seq. compensat-
ing factor RE/RL
6051
S3: K0
0.000 .. 4.000
1.000
S3: Zero seq. compensat-
ing factor K0
6052
S3: angle K0
-180.00 .. 180.00 °
0.00 °
S3: Zero seq. compensat-
ing angle of K0
Addr.
Parameter
C
Setting Options
Default Setting
Comments