Appendix
A.7 Settings
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
685
A.7
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding second-
ary nominal current of the current transformer.
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
201
CT Starpoint
P.System Data 1
towards Line
towards Busbar
towards Line
CT Starpoint
203
Unom PRIMARY
P.System Data 1
0.4 .. 1200.0 kV
400.0 kV
Rated Primary Voltage
204
Unom SECONDARY
P.System Data 1
80 .. 125 V
100 V
Rated Secondary Voltage (Ph-
Ph)
205
CT PRIMARY
P.System Data 1
10 .. 10000 A
1000 A
CT Rated Primary Current
206
CT SECONDARY
P.System Data 1
1A
5A
1A
CT Rated Secondary Current
207
SystemStarpoint
P.System Data 1
Solid Earthed
Peterson-Coil
Isolated
Solid Earthed
System Starpoint is
208A
1-1/2 CB
P.System Data 1
NO
YES
NO
1-1/2 Circuit breaker arrange-
ment
210
U4 transformer
P.System Data 1
Not connected
Udelta transf.
Usy2 transf.
Ux transformer
Not connected
U4 voltage transformer is
211
Uph / Udelta
P.System Data 1
0.10 .. 9.99
1.73
Matching ratio Phase-VT To
Open-Delta-VT
212
Usy2 connection
P.System Data 1
L1-E
L2-E
L3-E
L1-L2
L2-L3
L3-L1
L1-E
VT connection for Usy2
214A
ϕ
Usy2-Usy1
P.System Data 1
0 .. 360 °
0 °
Angle adjustment Usy2-Usy1
215
Usy1/Usy2 ratio
P.System Data 1
0.50 .. 2.00
1.00
Matching ratio Usy1 / Usy2
220
I4 transformer
P.System Data 1
Not connected
In prot. line
In paral. line
IY starpoint
In prot. line
I4 current transformer is
221
I4/Iph CT
P.System Data 1
0.010 .. 5.000
1.000
Matching ratio I4/Iph for CT's
230
Rated Frequency
P.System Data 1
50 Hz
60 Hz
50 Hz
Rated Frequency
236
Distance Unit
P.System Data 1
km
Miles
km
Distance measurement unit
237
Format Z0/Z1
P.System Data 1
RE/RL, XE/XL
K0
RE/RL, XE/XL
Setting format for zero seq.comp.
format
238A
EarthFltO/C 1p
P.System Data 1
stages together
stages separat.
stages together
Earth Fault O/C: setting for 1pole
AR
239
T-CB close
P.System Data 1
0.01 .. 0.60 sec
0.06 sec
Closing (operating) time of CB
240A
TMin TRIP CMD
P.System Data 1
0.02 .. 30.00 sec
0.10 sec
Minimum TRIP Command Dura-
tion
241A
TMax CLOSE CMD
P.System Data 1
0.01 .. 30.00 sec
1.00 sec
Maximum Close Command Du-
ration
242
T-CBtest-dead
P.System Data 1
0.00 .. 30.00 sec
0.10 sec
Dead Time for CB test-autoreclo-
sure
251
K_ALF/K_ALF_N
P.System Data 1
1.00 .. 10.00
1.00
k_alf/k_alf nominal
253
E% ALF/ALF_N
P.System Data 1
0.5 .. 50.0 %
5.0 %
CT Error in % at k_alf/k_alf
nominal
254
E% K_ALF_N
P.System Data 1
0.5 .. 50.0 %
15.0 %
CT Error in % at k_alf nominal
301
ACTIVE GROUP
Change Group
Group A
Group B
Group C
Group D
Group A
Active Setting Group is