Appendix
A.7 Settings
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
692
1920
ϕ
>
Dis. General
30 .. 60 °
50 °
PHI> pickup (lower setpoint)
1921
ϕ
<
Dis. General
90 .. 120 °
110 °
PHI< pickup (upper setpoint)
1930A
1ph FAULTS
Dis. General
PHASE-EARTH
PHASE-PHASEONLY
PHASE-EARTH
1ph-pickup loop selection (PU
w/o earth)
2002
P/S Op. mode
Power Swing
All zones block
Z1/Z1B block
>= Z2 block
Z1,Z1B,Z2 block
All zones block
Power Swing Operating mode
2006
PowerSwing trip
Power Swing
NO
YES
NO
Power swing trip
2101
FCT Telep. Dis.
Teleprot. Dist.
ON
OFF
ON
Teleprotection for Distance pro-
tection
2102
Type of Line
Teleprot. Dist.
Two Terminals
Three terminals
Two Terminals
Type of Line
2103A
Send Prolong.
Teleprot. Dist.
0.00 .. 30.00 sec
0.05 sec
Time for send signal prolongation
2107A
Delay for alarm
Teleprot. Dist.
0.00 .. 30.00 sec
10.00 sec
Time Delay for Alarm
2108
Release Delay
Teleprot. Dist.
0.000 .. 30.000 sec
0.000 sec
Time Delay for release after
pickup
2109A
TrBlk Wait Time
Teleprot. Dist.
0.00 .. 30.00 sec;
∞
0.04 sec
Transient Block.: Duration exter-
nal flt.
2110A
TrBlk BlockTime
Teleprot. Dist.
0.00 .. 30.00 sec
0.05 sec
Transient Block.: Blk.T. after ext.
flt.
2112A
DIS TRANSBLK EF
Teleprot. Dist.
YES
NO
YES
DIS transient block by EF
2113
Mem.rec.sig.
Teleprot. Dist.
YES
NO
NO
Memorize receive signal
2201
FCT Direct Trip
DTT Direct Trip
ON
OFF
OFF
Direct Transfer Trip (DTT)
2202
Trip Time DELAY
DTT Direct Trip
0.00 .. 30.00 sec;
∞
0.01 sec
Trip Time Delay
2301
INRUSH REST.
Diff. Prot
OFF
ON
OFF
Inrush Restraint
2302
2nd HARMONIC
Diff. Prot
10 .. 45 %
15 %
2nd. harmonic in % of fundamen-
tal
2303
CROSS BLOCK
Diff. Prot
NO
YES
NO
Cross Block
2305
MAX INRUSH PEAK
Diff. Prot
1A
1.1 .. 25.0 A
15.0 A
Maximum inrush-peak value
5A
5.5 .. 125.0 A
75.0 A
2310
CROSSB 2HM
Diff. Prot
0.00 .. 60.00 sec;
∞
0.00 sec
Time for Crossblock with 2nd
harmonic
2401
FCT HS/SOTF-O/C
SOTF Overcurr.
ON
OFF
ON
Inst. High Speed/SOTF-O/C is
2404
I>>>
SOTF Overcurr.
1A
0.10 .. 15.00 A;
∞
1.50 A
I>>> Pickup
5A
0.50 .. 75.00 A;
∞
7.50 A
2405A
I>>>>
SOTF Overcurr.
1A
1.00 .. 25.00 A;
∞
∞
A
I>>>> Pickup
5A
5.00 .. 125.00 A;
∞
∞
A
2406
CBaux for I>>>
SOTF Overcurr.
local only
local and rem.
local and rem.
CB-aux check for activation of
I>>>
2501
FCT Weak Infeed
Weak Infeed
OFF
ECHO only
ECHO and TRIP
Echo &Trip(I=0)
ECHO only
Weak Infeed function
2502A
Trip/Echo DELAY
Weak Infeed
0.00 .. 30.00 sec
0.04 sec
Trip / Echo Delay after carrier
receipt
2503A
Trip EXTENSION
Weak Infeed
0.00 .. 30.00 sec
0.05 sec
Trip Extension / Echo Impulse
time
2504A
Echo BLOCK Time
Weak Infeed
0.00 .. 30.00 sec
0.05 sec
Echo Block Time
2505
UNDERVOLTAGE
Weak Infeed
2 .. 70 V
25 V
Undervoltage (ph-e)
2509
Echo:1channel
Weak Infeed
NO
YES
NO
Echo logic: Dis and EF on
common channel
2510
Uphe< Factor
Weak Infeed
0.10 .. 1.00
0.70
Factor for undervoltage Uphe<
2511
Time const.
τ
Weak Infeed
1 .. 60 sec
5 sec
Time constant Tau
2512A
Rec. Ext.
Weak Infeed
0.00 .. 30.00 sec
0.65 sec
Reception extension
2513A
T 3I0> Ext.
Weak Infeed
0.00 .. 30.00 sec
0.60 sec
3I0> exceeded extension
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments