Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
295
Parameter
Function
Range
Factory
default
Can be
changed
Scaling Data
set
Data
type
Acc.
Level
P2186[0...2]
Lower torque threshold 1
[Nm]
0.0 - 99999.0
0.0
U, T
-
DDS
Float 3
Lower limit threshold value 1 for comparing actual torque.
Dependency: See P2181 for calculated default value.
P2187[0...2]
Upper torque threshold 2
[Nm]
0.0 - 99999.0
Value in
r0333
U, T
-
DDS
Float 3
Upper limit threshold value 2 for comparing actual torque.
Dependency: This parameter is influenced by automatic calculations defined by P0340.
See P2181 for calculated default value.
Note:
See P2185
P2188[0...2]
Lower torque threshold 2
[Nm]
0.0 - 99999.0
0.0
U, T
-
DDS
Float 3
Lower limit threshold value 2 for comparing actual torque.
Dependency: See P2181 for calculated default value.
P2189[0...2] Upper torque threshold 3
[Nm]
0.0 - 99999.0
Value in
r0333
U, T
-
DDS
Float 3
Upper limit threshold value 3 for comparing actual torque.
Dependency: This parameter is influenced by automatic calculations defined by P0340.
See P2181 for calculated default value.
Note:
See P2185
P2190[0...2]
Lower torque threshold 3
[Nm]
0.0 - 99999.0
0.0
U, T
-
DDS
Float 3
Lower limit threshold value 3 for comparing actual torque.
Dependency: See P2181 for calculated default value.
P2192[0...2]
Load monitoring delay time
[s]
0 - 65
10
U, T
-
DDS
U16
3
P2192 defines a delay before warning/trip becomes active.
- It is used to eliminate events caused by transient conditions.
- It is used for both methods of fault detection.
r2197.0...12
CO/BO: Monitoring word 1
-
-
-
-
-
U16
3
Monitoring word 1 which indicates the state of monitor functions. Each bit represents one monitor function.
Bit
Signal name
1 signal
0 signal
00
|f_act| <= P1080 (f_min)
Yes
No
01
|f_act| <= P2155 (f_1)
Yes
No
02
|f_act| > P2155 (f_1)
Yes
No
03
f_act >= zero
Yes
No
04
f_act >= setp. (f_set)
Yes
No
05
|f_act| <= P2167 (f_off)
Yes
No
06
|f_act| >= P1082 (f_max)
Yes
No
07
f_act == setp. (f_set)
Yes
No
08
Act. current |r0027| >= P2170
Yes
No
09
Act. unfilt. Vdc < P2172
Yes
No
10
Act. unfilt. Vdc > P2172
Yes
No
11
Output load is not present
Yes
No
12
|f_act| > P1082 with delay
Yes
No