Parameter list
8.2 Parameter list
SINAMICS V20 Converter
234
Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling Data
set
Data
type
Acc.
Level
r0774[0]
Actual analog output
value [V] or [mA]
-
-
-
-
-
Float 2
Shows value of analog output after filtering and scaling.
Index:
See P0771
Note:
The analog output is only a current output. By connecting an external resistor of 500 Ω to the terminals
(4/5) a voltage output with a range of 0 V to 10 V can be created.
P0775[0]
Permit absolute value of
analog output
0 - 1
0
T
-
-
U16
2
Decides if the absolute value of the analog output is used. If enabled, this parameter will take the absolute
value to be outputted. If the value was originally negative then the corresponding bit in r0785 is set, oth-
erwise it is cleared.
Index:
See P0771
P0777[0]
Value x1 of analog out-
put scaling [%]
-99999 - 99999 0.0
U, T
-
-
Float 2
Defines x1 output characteristic. Scaling block is responsible for adjustment of output value defined in
P0771 (analog output connector input). x1 is the first value of the two pairs of variants x1/y1 and x2/y2
which determine the straight line. The two points P1 (x1, y1) and P2 (x2, y2) can be chosen freely.
Note:
See P0771
Dependency: See P0758
P0778[0]
Value y1 of analog out-
put scaling
0 - 20
0
U, T
-
-
Float 2
Defines y1 of output characteristic.
Index:
See P0771
P0779[0]
Value x2 of analog out-
put scaling [%]
-99999 - 99999 100.0
U, T
-
-
Float 2
Defines x2 of output characteristic.
Index:
See P0771
Dependency: See P0758
P0780[0]
Value y2 of analog out-
put scaling
0 - 20
20
U, T
-
-
Float 2
Defines y2 of output characteristic.
Index:
See P0771
P0781[0]
Width of analog output
deadband
0 - 20
0
U, T
-
-
Float 2
Sets width of dead-band for analog output.
Index:
See P0771
r0785.0
CO/BO: Status word of
analog output
-
-
-
-
-
U16
2
Displays status of analog output. Bit 0 indicates that the value of analog output 1 is negative.
Bit
Signal name
1 signal
0 signal
00
Analog output 1 negative
Yes
No
Summary of Contents for SINAMICS V20 Inverter