Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
305
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P2360[0...2] Enable cavitation protec-
tion
0 - 2
0
U, T
-
DDS
U16 2
Cavitation protection enabled.
Will generate a fault/warning when cavitation conditions are deemed to be present.
0
Disable
1
Fault
2
Warn
P2361[0...2] Cavitation threshold [%]
0.00 - 200.00
40.00
U, T
-
DDS
Float 2
Feedback threshold over which a fault/warning is triggered, as a percentage (%).
P2362[0...2]
Cavitation protection time [s]
0 - 65000
30
U, T
-
DDS
U16 2
The time for which cavitation conditions have to be present before a fault/warning is triggered.
P2365[0...2]
Hibernation enable/disable
0 - 2
0
U, T
-
DDS
U16 2
Select or disable the hibernation functionality.
0
Disabled
1
Frequency hibernation (The converter uses the frequency setpoint as the
wakeup trigger. You can use P2366 and P2367 to configure this function.)
2
PID hibernation (The converter uses the PID error as the wakeup trigger. You
can use P2390, P2391, and P2392 to configure this function.)