Technical specifications
SINAMICS V20 Converter
346
Operating Instructions, 10/2019, A5E34559884-012
Overload capability
Power rating (kW)
Average output current Overload current
Maximum overload cycle
0.12 to 15
100% rated
150% rated for 60 seconds 150% rated for 60 seconds followed by
94.5% rated for 240 seconds
18.5 (HO)/22 (HO)
22 (LO)/30 (LO)
110% rated for 60 seconds 110% rated for 60 seconds followed by
more than 98% rated for 240 seconds
EMC requirements
Note
Install all converters in accordance with the manufacturer’s guidelines and in accordance
with good EMC practices.
Use copper screened cable. For the maximum motor cable lengths, refer to Section
"Terminal description (Page 40)".
Do not exceed the default switching frequency.
Three phase AC 400 V converters
Single phase AC 230 V converters
ESD
EN 61800-3
EN 61800-3
Radiated immunity
Burst
Surge
Conducted immunity
Voltage distortion immunity
Conducted emissions
Three phase AC 400 V filtered converters:
EN 61800-3 Category C2/C3
Single phase AC 230 V filtered converters:
EN 61800-3 Category C1/C2
Radiated emissions
Maximum power losses
Three phase AC 400 V converters
Frame size
FSA
FSB
FSC FSD
FSE
Power
rating
(kW)
0.37 0.55 0.75 1.1 1.5 2.2 3
4
5.5
7.5 11 15 18.5 22 22 30
HO LO HO LO
(hp)
0.75 0.75 1
1.5 2
3
5
5
7.5
10 15 20 25
30 30 40
HO LO HO LO
Maximum power loss (w)
1)
25
28
33
43 54 68 82
100
145 180 276 338 387 475 457 626
1)
With I/O fully loaded
Single phase AC 230 V converters
Frame size
FSAA/FSAB
FSAC
FSAD
FSC
Power
rating
(kW)
0.12
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3.0
2.2
3.0
(hp)
0.17
0.33
0.5
0.75
1
1.5
2
3
4
3
4
Maximum power
loss (w)
1)
14
22
29
39
48
57
87
138
177
138
177
1)
With I/O fully loaded