Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
75
Connection macro Cn009 - PID control with the fixed value reference
Connection macro settings:
Parameter Description
Factory default
Default for Cn009
Remarks
P0700[0] Selection of command source
1
2
Terminals as command source
P0701[0] Function of digital input 1
0
1
ON/OFF
P0702[0] Function of digital input 2
0
15
DI2 = PID fixed value 1
P0703[0] Function of digital input 3
9
16
DI3 = PID fixed value 2
P0704[0] Function of digital input 4
15
17
DI4 = PID fixed value 3
P2200[0] BI: Enable PID controller
0
1
Enable PID
P2201[0] Fixed PID setpoint 1 [%]
10
10
-
P2202[0] Fixed PID setpoint 2 [%]
20
20
-
P2203[0] Fixed PID setpoint 3 [%]
50
50
-
P2216[0] Fixed PID setpoint mode
1
1
Direct selection
P2220[0] BI: Fixed PID setpoint select bit 0 722.3
722.1
BICO connection DI2
P2221[0] BI: Fixed PID setpoint select bit 1 722.4
722.2
BICO connection DI3
P2222[0] BI: Fixed PID setpoint select bit 2 722.5
722.3
BICO connection DI4
P2253[0] CI: PID setpoint
0
2224
PID setpoint = fixed value
P2264[0] CI: PID feedback
755.0
755.1
PID feedback = AI2