Commissioning via the built-in BOP
5.7 Restoring to defaults
SINAMICS V20 Converter
138
Operating Instructions, 10/2019, A5E34559884-012
5.7
Restoring to defaults
Restoring to factory defaults
Parameter
Function
Setting
P0003
User access level
= 1 (standard user access level)
P0010
Commissioning parameter
= 30 (factory setting)
P0970
Factory reset
= 21: parameter reset to factory defaults deleting user defaults if
stored
Restoring to user defaults
Parameter
Function
Setting
P0003
User access level
= 1 (standard user access level)
P0010
Commissioning parameter
= 30 (factory setting)
P0970
Factory reset
= 1: parameter reset to user defaults if stored, else factory de-
faults
After setting the parameter P0970, the converter displays "8 8 8 8 8" and then the screen
shows "P0970". P0970 and P0010 are automatically reset to their original value 0.