Parameter list
8.2 Parameter list
SINAMICS V20 Converter
200
Operating Instructions, 10/2019, A5E34559884-012
Parameter
Function
Range
Factory
default
Can be
changed
Scaling Data set Data
type
Acc.
Level
P0013[0...19] User-defined parame-
ter
0 - 65535
[0...16] 0
[17] 3
[18] 10
[19] 12
U, T
-
-
U16 3
Defines a limited set of parameters to which the end user has access.
Instructions for use:
1.
Set P0003 = 3 (expert user).
2.
Go to P0013 indices 0 to 16 (user list)
3.
Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list.
The following values are fixed and cannot be changed:
- P0013 index 17 = 3 (user access level)
- P0013 index 18 = 10 (commissioning parameter filter)
- P0013 index 19 = 12 (key for user defined parameter)
4.
Set P0003 = 0 to activate the user defined parameter.
Index:
[0]
1st user parameter
[1]
2nd user parameter
...
...
[19]
20th user parameter
Dependency: First,
set P0011 ("lock") to a different value then P0012 ("key") to prevent changes to user-defined parameter.
Then, set P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter
(and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
P0014[0...2] Store mode
0 - 1
0
U, T
-
-
U16 3
Sets the store mode for parameters. The store mode can be configured for all interfaces under "Index".
0
Volatile ( RAM)
1
Non-volatile (EEPROM)
Index:
[0]
USS/Modbus on RS485
[1]
USS on RS232 (reserved)
[2]
Reserved
Note:
An independent store request may be part of the serial communications (for example, PKE bits 15-12 of
USS protocol). See the table below for an influence on the settings of P0014.
Value of P0014 [x]
Store request via USS
Result
RAM
EEPROM
EEPROM
EEPROM
EEPROM
EEPROM
RAM
RAM
RAM
EEPROM
RAM
EEPROM
1.
P0014 itself will always be stored in the EEPROM.
2.
P0014 will not be changed by performing a factory reset.
When transferring parameter P0014, the converter uses its processor to carry-out internal calculations.
Communications - both via USS as well as Modbus - are interrupted for the time that it takes to make
these calculations.