Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
70
Operating Instructions, 10/2019, A5E34559884-012
Connection macro Cn004 - Fixed speeds in binary mode
Fixed speeds with ON command in binary mode
Up to 16 different fixed frequency values (0 Hz, P1001 to P1015) can be selected by the
fixed frequency selectors (P1020 to P1023). For more information about the fixed
frequencies in binary mode, see the parameter descriptions of P1001 to P1016 in Section
"Parameter list (Page 198)".
Connection macro settings:
Parameter Description
Factory default Default for Cn004 Remarks
P0700[0] Selection of command source
1
2
Terminals as command source
P1000[0] Selection of frequency
1
3
Fixed frequency
P0701[0] Function of digital input 1
0
15
Fixed speed bit 0
P0702[0] Function of digital input 2
0
16
Fixed speed bit 1
P0703[0] Function of digital input 3
9
17
Fixed speed bit 2
P0704[0] Function of digital input 4
15
18
Fixed speed bit 3
P1001[0] Fixed frequency 1
10
10
Fixed speed 1
P1002[0] Fixed frequency 2
15
15
Fixed speed 2
P1003[0] Fixed frequency 3
25
25
Fixed speed 3
P1004[0] Fixed frequency 4
50
50
Fixed speed 4
P1016[0] Fixed frequency mode
1
2
Binary mode
P0840[0] BI: ON/OFF1
19.0
1025.0
Converter starts at the fixed speed
selected
P1020[0] BI: Fixed frequency selection bit 0 722.3
722.0
DI1
P1021[0] BI: Fixed frequency selection bit 1 722.4
722.1
DI2
P1022[0] BI: Fixed frequency selection bit 2 722.5
722.2
DI3
P1023[0] BI: Fixed frequency selection bit 3 722.6
722.3
DI4
P0771[0] CI: Analog output
21
21
Actual frequency
P0731[0] BI: Function of digital output 1
52.3
52.2
Converter running
P0732[0] BI: Function of digital output 2
52.7
52.3
Converter fault active