Communicating with the PLC
7.2 MODBUS communication
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
185
Response for unsuccessful write operation - write request still not completed
Value
Byte
Description
11 h 1
Slave address
03 h
20 h
0001 h
2F00 h
0004 h
2
3
4,5
6,7
8,9
Function code (read)
Number of following data bytes (20 h: 32 bytes
≙
16 regis-
ters)
40601: DS47 Control = 1 (request is processed)
40602: Function 2F h(47), response length 0 (fault)
40603: Error code: 0004 Response Not Ready (response has
still not been issued)
xx h
xx h
10
11
CRC "Low"
CRC "High"
Exception Responses
If an error is detected through the MODBUS processing, the slave will respond with the FC
of the request, but with most significant bit of the FC high and with the Exception Code in the
data field. However, any error detected on the global address 0 does not result in a response
since all slaves cannot respond at once.
If an error is detected within the received message (for example, parity error, incorrect CRC
and so on), then NO response is sent to the master.
Note that if a request with FC16 is received which contains a write that the converter cannot
perform (including write to a zero entry), other valid writes will still be performed even though
an exception response is returned.
The following MODBUS Exception Codes are supported by SINAMICS V20:
Exception Code MODBUS name
Meaning
01
Illegal function code
The function code is not supported – only FC3, FC6 and
FC16 are supported.
02
Illegal data address
An invalid address was queried.
03
Illegal data value
An invalid data value was recognized.
04
Slave device failure
An unrecoverable error occurred while the device was
processing the action.
The table below shows the cases in which an Exception Code is returned:
Error description
Exception Code
Unknown Function Code
01
Read registers, which are out of boundary
02
Write register, which is out of boundary
02
Read request of too many registers (>125)
03
Write request of too many registers (>123)
03
Incorrect message length
03
Write to a read-only register
04
Write register, error in parameter access
04
Read register, error in Parameter Manager
04
Write to a zero entry
04
Unknown error
04