Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
201
Parameter
Function
Range
Factory
default
Can be
changed
Scaling Data set Data
type
Acc.
Level
r0017
CO/BO: BOP button
status
-
-
-
-
-
U16 3
Shows the immediate status of the BOP buttons.
Bit
Signal name
1 signal
0 signal
00
Run button
Yes
No
01
Stop button
Yes
No
02
HAND/AUTO button combination (OK + M)
Yes
No
03
OK button
Yes
No
05
Up button
Yes
No
06
Down button
Yes
No
07
Run/stop latch
Yes
No
Note:
Bit 07 (ON/OFF), will remain high if the run button has been pressed and released. It will only be reset
once the stop button has been pressed.
r0018
Firmware version
-
-
-
-
-
Float 1
Displays version number of installed firmware.
r0019.0...14 CO/BO: Operator
panel control word
-
-
-
-
-
U16 3
Displays status of operator panel commands. The settings below are used as the "source" codes for key-
pad control when connecting to BICO input parameters.
Bit
Signal name
1 signal
0 signal
00
ON/OFF1
Yes
No
01
OFF2: Electrical stop
No
Yes
08
JOG right
Yes
No
11
Reverse (setpoint inversion)
Yes
No
13
Motor potentiometer MOP up
Yes
No
14
Motor potentiometer MOP down
Yes
No
Note:
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual
status of the relevant command.
r0020
CO: Frequency set-
point before RFG [Hz]
-
-
-
-
-
Float 3
Displays actual frequency setpoint (input of ramp function generator). This value is available filtered
(r0020) and unfiltered (r1119). The actual frequency setpoint after RFG is displayed in r1170.
r0021
CO: Actual filtered
frequency [Hz]
-
-
-
-
-
Float 2
Displays actual converter output frequency (r0024) excluding slip compensation (and resonance damping,
frequency limitation in V/f mode).
r0022
Actual filtered rotor
speed [RPM]
-
-
-
-
-
Float 3
Displays calculated rotor speed based on r0021 (filtered output frequency [Hz] x 120/number of poles). The
value is updated every 128 ms.
Note:
This calculation makes no allowance for load-dependent slip.
r0024
CO: Actual filtered
output frequency [Hz]
-
-
-
-
-
Float 3
Displays actual filtered output frequency (slip compensation, resonance damping and frequency limitation
are included). See also r0021. This value is available filtered (r0024) and unfiltered (r0066).