Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
225
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P0704[0...2]
Function of digital input 4 0 - 99
15
T
-
CDS U16 2
Selects function of digital input 4.
See P0701.
P0705[0...2]
Function of digital input 5 0 - 99
16
T
-
CDS U16 2
Selects function of digital input 5.
See P0701.
Note:
This digital input is provided by the optional I/O Extension Module.
P0706[0...2]
Function of digital input 6 0 - 99
17
T
-
CDS U16 2
Selects function of digital input 6.
See P0701.
Note:
This digital input is provided by the optional I/O Extension Module.
P0712[0...2]
Analog/digital input 1
0 - 99
0
T
-
CDS U16 2
Selects function of digital input AI1 (via analog input).
See P0701.
Note:
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
P0713[0...2]
Analog/digital input 2
0 - 99
0
T
-
CDS U16 2
Selects function of digital input AI2 (via analog input).
See P0701.
Note:
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
P0717
Connection macro
0 - 255
0
C(1)
-
-
U16 1
Selects a given connection macro, which is a set of parameter values for a given set of control connec-
tions. There are a number of connection macros which define basic control connection settings such as
Terminals, BOP, PID with analog setpoint etc.
Note:
Please note that to guarantee correct setting of the Connection macro, the Connection macro number
should only be changed during Setup directly after a parameter reset.
P0719[0...2]
Selection of command &
frequency setpoint
0 - 57
0
T
-
CDS U16 4
Central switch to select control command source for converter. Switches command and setpoint source
between freely programmable BICO parameters and fixed command/setpoint profiles. Command and
setpoint sources can be changed independently. The tens digit chooses the command source and the
units digit chooses the setpoint source.
0
Cmd = BICO parameter, Setpoint = BICO parameter
1
Cmd = BICO parameter, Setpoint = MOP setpoint
2
Cmd = BICO parameter, Setpoint = Analog setpoint
3
Cmd = BICO parameter, Setpoint = Fixed frequency
4
Cmd = BICO parameter, Setpoint = USS on RS232 (reserved)
5
Cmd = BICO parameter, Setpoint = USS/MODBUS on RS485
7
Cmd = BICO parameter, Setpoint = Analog setpoint 2
40
Cmd = USS on RS232 (reserved), Setpoint = BICO parameter
41
Cmd = USS on RS232 (reserved), Setpoint = MOP setpoint
42
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint
43
Cmd = USS on RS232 (reserved), Setpoint = Fixed frequency
44
Cmd = USS on RS232 (reserved), Setpoint = USS on RS232 (reserved)