Commissioning via the built-in BOP
5.5 Quick commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
81
Restrictions on the estimated quick commissioning:
–
This functionality is recommended at the rated supply voltage.
–
This functionality is designed around the data for Siemens motors 1LE0001, 1TL0001,
1LE1 and 1LA7 although it may make reasonable approximations for other motor
types.
–
This functionality gives an estimate of the motor data values; however, if the motor is
to operate near the limits of its capability (rated power and current), then you must
carry out the conventional quick commissioning.
–
The value calculations only work with motors connected in star configuration and
assume the supply frequency is 50 Hz.
–
The calculations use the DC link voltage measurement and thus only work if mains is
connected.
–
The calculations are accurate only for 4-pole motors.
–
The 87 Hz characteristic is not supported.
Setting parameters
Note
In the table below, "●" indicates that you must enter the
value of this parameter according to
the rating plate of the motor when you carry out the conventional quick commissioning.
Parameters for
conventional
quick commis-
sioning
Parameters for
estimated quick
commissioning
Function
Setting
P0003 = 3
P0003 = 3
User access level
= 3 (Expert access level)
P0010 = 1
P0010 = 1
Commissioning parameter = 1 (quick commissioning)
P0100
P0100 = 0
50/60 Hz selection
Set a value, if necessary:
=0: Europe [kW], 50 Hz (factory default)
=1: North America [hp], 60 Hz
=2: North America [kW], 60 Hz
Note:
Set this parameter to 0 if you want to carry out the esti-
mated quick commissioning.
P0301 = 0
P0301 > 0
Rated motor power [kW]
Range: 0 to 2000
= 0: Conventional quick commissioning (factory default)
> 0: Estimated quick commissioning
Once you set this parameter to a non-zero value, you
only need to enter the rated motor power and then the
converter calculates and sets the values of the rest of
the motor data (P0304, P0305, P0307, P0308, P0310
and P0311).
P0304[0] ●
-
Rated motor voltage [V]
Range: 10 to 2000
Note:
The input of rating plate data must correspond with the
wiring of the motor (star/delta).