Commissioning via the built-in BOP
5.6 Function commissioning
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
95
Sequence 2
1.
Enabled and selected with the BICO parameter P1230 (see figure below).
2.
The converter pulses are inhibited for the duration of the de-magnetizing time P0347.
3.
The requested braking current P1232 is impressed for the time selected and the motor is
braked. This state is displayed using signal r0053 bit 00.
4.
After DC braking has been cancelled, the converter accelerates back to the setpoint
frequency until the motor speed matches the converter output frequency.