Technical data
6.2 Ambient conditions
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
75
6.2
Ambient conditions
Property
Version
Ambient conditions for transport in the transport packaging
Air-conditioning
- 40° C … + 70° C, according to Class 2K4 to EN 60721-3-2:1997
maximum humidity 95% at 40 °C
Mechanical system
Shock and vibration permissible according to 1M2 to IEC 60721-3-2:1997
Chemical substances
Protected according to Class 2C2 to IEC 60721-3-2:1997
Biological ambient condi-
tions
Suitable according to Class 2B1 to IEC 60721-3-2:1997
Ambient conditions for long-term storage in the product packaging or in transport packaging
Air-conditioning
- 25 °C … + 55° C, according to Class 1K3 to IEC 60721-3-1:1997
Chemical substances
Protected according to Class 1C2 to IEC 60721-3-1:1997
Biological ambient condi-
tions
Suitable according to Class 1B1 to IEC 60721-3-1:1997
Ambient conditions in operation
Installation altitude
Up to 1000 m above sea level without limitations
Restrictions for special ambient conditions (Page 105)
Air-conditioning
1)
•
FSA ... FSC ambient operating temperature
2)
–
For operation according to Low Overload: -10 °C … +40 °C
–
For operation according to High Overload: -10 °C … +50 °C
–
Restrictions for special ambient conditions (Page 105)
•
FSD ... FSG ambient operating temperature
2)
–
For operation according to Low Overload: -20 °C … +40 °C
–
For operation according to High Overload: -20 °C … +50 °C
–
Restrictions for special ambient conditions (Page 105)
•
Relative humidity: 5 … 95%, condensation not permitted
•
Oil mist, ice formation, condensation, dripping water, spraying water, splashing water
and water jets are not permitted
Mechanical system
Vibration test during operation according to IEC 60068-2-6 Test Fc (sinusoidal)
•
0 ... 57 Hz: 0.075 mm deflection amplitude
•
57 ... 150 Hz: 1 g acceleration amplitude
•
10 frequency cycles per axis
Shock test according to IEC 60068-2-27 Test Ea (half-sine)
•
5 g peak acceleration
•
30 ms duration
•
3 shocks in all three axes in both directions
Chemical substances
•
FSA … FSC: Protected according to 3C2 to IEC 60721-3-3:2002
•
FSD … FSG: Protected according to 3C3 to IEC 60721-3-3:2002
Biological ambient condi-
tions
Suitable according to 3B1 to IEC 60721-3-3: 2002
Pollution
Suitable for environments with degree of pollution 2 according to EN 61800-5-1
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......