Accessories
8.2 Mounting frames for PT power modules
Power Module PM240-2
118
Hardware Installation Manual, 01/2020, A5E33294624B AL
8.2
Mounting frames for PT power modules
Article numbers for mounting frames
●
FSA: 6SL3260-6AA00-0DA0
●
FSB: 6SL3260-6AB00-0DA0
●
FSC: 6SL3260-6AC00-0DA0
●
FSD: 6SL3200-0SM17-0AA0
●
FSE: 6SL3200-0SM18-0AA0
●
FSF: 6SL3200-0SM20-0AA0
All of the necessary nuts and seals are included in the scope of delivery.
NOTICE
Damage to devices due to defective mounting frame seals
If seals are defective, liquid or dirt can enter the control cabinet. This can damage or even
destroy devices.
•
Check the seals for damage.
•
Replace any damaged seals.
WARNING
Spread of fire from the rear side of the converter
In the event of fire outbreak, the rear side of the converter installed with the push-through
mounting frame cannot prevent the escape of fire and smoke. This can result in serious
personal injury or property damage.
•
Install a metal rear air channel that prevents the spread of fire and smoke, or take other
appropriate measures to protect personnel.
•
Ensure that smoke can only escape via controlled and monitored paths.