Connecting
4.1 Permissible line supplies
Power Module PM240-2
48
Hardware Installation Manual, 01/2020, A5E33294624B AL
4.1.2
TT line system
In a TT line system, the transformer ground-
ing and the installation grounding are inde-
pendent of one another.
There are TT line supplies where the neutral
conductor N is either transferred – or not.
Note
Operation in IEC or UL systems
For installations in compliance with IEC, operation on TT line systems is permissible. For
installations in compliance with UL, operation on TT line systems is not permissible.
Converters connected to a TT system
●
Converters with integrated line filter:
–
Operation on TT line systems with grounded neutral point permissible.
–
Operation on TT line systems without grounded neutral point not permissible.
Note
Special feature of FSG converters
FSG converters with integrated C3 line filter can be operated in TT line systems
without a grounded neutral point if you remove the screw for functional grounding.
Figure 4-2 Remove screw for functional grounding (Page 46)
If you remove the screw for functional grounding, the EMC properties deteriorate and
the requirements of Class C3 are no longer met.
●
Converters with external line filter:
–
Operation on TT line systems with grounded neutral point permissible.
–
Operation on TT line systems without grounded neutral point not permissible.
●
Converters without line filter:
–
Operation on all TT line systems permissible.
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......