Technical data
6.5 400 V converters
Power Module PM240-2
90
Hardware Installation Manual, 01/2020, A5E33294624B AL
Table 6- 16 PM240-2, IP20, frame size A, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3210-1PE14-3UL1
6SL3210-1PE14-3AL1
6SL3210-1PE16-1UL1
6SL3210-1PE16-1AL1
6SL3210-1PE18-0UL1
6SL3210-1PE18-0AL1
LO base load power
1.5 kW
2.2 kW
3.0 kW
LO base load input current
5.5 A
7.7 A
10.1 A
LO base load output current
4.1 A
5.9 A
7.7 A
HO base load power
1.1 kW
1.5 kW
2.2 kW
HO base load input current
4.7 A
6.1 A
8.8 A
HO base load output current
3.1 A
4.1 A
5.9 A
Fuse according to IEC
Fuse according to UL, class J
3NA3805 (16 A)
15 A
3NA3805 (16 A)
15 A
3NA3805 (16 A)
15 A
Power loss
0.07 kW
0.1 kW
0.12 kW
Required cooling air flow
5 l/s
5 l/s
5 l/s
Weight without filter
1.4 kg
1.4 kg
1.4 kg
Weight with filter
1.6 kg
1.6 kg
1.6 kg
Table 6- 17 PM240-2, PT, frame size A, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3211-1PE18-0UL1
6SL3211-1PE18-0AL1
LO base load power
3.0 kW
LO base load input current
10.1 A
LO base load output current
7.7 A
HO base load power
2.2 kW
HO base load input current
8.8 A
HO base load output current
5.9 A
Fuse according to IEC
Fuse according to UL, class J
3NA3805 (16 A)
15 A
Power loss without filter
0.12 kW
1)
Required cooling air flow
7 l/s
Weight without filter
1.8 kg
Weight with filter
2.0 kg
1) approx. 0.1 kW through the heatsink
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......