Installing
3.4 Mounting the Power Modules
Power Module PM240-2
34
Hardware Installation Manual, 01/2020, A5E33294624B AL
Table 3- 5
Dimensions depend on the Control Unit (CU) and HMI device [mm]
Frame
size
Width
[mm]
Height [mm]
Overall depth in the cabinet [mm]
Without
shield plate
With shield
plate
T1
with
CU230P-
2
1)
with
CU240B-2
1)
/
CU240E-2
1)
with
CU250S-
2
1)
FSA
126
238
322
118
177
159
180
FSB
154
345
430
118
177
159
180
FSC
200
411
500
118
177
159
180
1)
With a Smart Access Module plus 9 mm
With blanking cover or with Operator Panel plus 11 mm.
Table 3- 6
Cooling air clearances and additional dimensions
Frame
size
Power Module depth [mm]
Cooling air clearances [mm]
1)
T1 + T2
T1
T2
Top
Bottom
Front
FSA … F
SC
171
118
53
80
100
100
1)
The Power Module is designed for mounting without any lateral cooling air clearance. For toler-
ance reasons, we recommend a lateral clearance of 1 mm.
Table 3- 7
Electrical cabinet cutout and mounting
Frame
size
Control cabinet cutout [mm]
Fixing/torque [Nm]
a
b
c
d
e
FSA
103
106
27
198
88
8 × M5 / 3.5
FSB
148
134
34.5
304
116
8 × M5 / 3.5
FSC
123
174
30.5
365
156
10 × M5 / 3.5
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......