Accessories
8.12 dv/dt filter plus VPL
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
161
Article number JTA: TEF1203
-0GB
-0HB
-0JB
Voltage drop
17.15 V
17.13 V
17.97 V
Rated DC link voltage
935 V
935 V
935 V
Maximum voltage rise at motor ter-
minals
1)
< 500 V/
μ
s
< 500 V/
μ
s
< 500 V/
μ
s
Maximum peak voltage at motor
terminals (phase to phase)
2)
1350 V
1350 V
1350 V
Maximum peak voltage at motor
terminals (phase to earth)
2)
1100 V
1100 V
1100 V
Maximum cable length filter - motor
(screened / unscreened)
350 m / 525 m
350 m / 525 m
350 m / 525 m
Terminal type
Screw terminals
Screw terminals
Screw terminals
Rated terminal cross section (load
circuit)
16 mm²
35 mm²
50 mm²
Rated terminal cross section (DC
link feedback)
3)
16 mm²
16 mm²
16 mm²
Degree of protection
4)
IP00
IP00
IP00
Ambient temperature
5)
-20°C to 40°C
-20°C to 40°C
-20°C to 40°C
Weight
20 kg
29 kg
46 kg
Connection
Metrical (mm² / Nm)
Imperial (AWG / lbf.in)
Stripping length (mm)
Line / motor cable
16 / 1.2
6 / 11.0
13
35 / 2.5
2 / 22
17
70 / 6.0
2/0 / 53
24
DC link
16 / 1.2
6 / 11.0
13
16 / 1.2
6 / 11
13
16 / 1.2
6 / 11
13
Ground
16 / 1.2
6 / 11.0
13
35 / 2.5
2 / 22
17
70 / 10.0
2/0 / 86
24
1)
Voltage rise according IEC/TS 60034-17
2)
Under nominal DC link voltage
3)
Short-circuit-proof wiring is required
4)
Installing the filter in an enclosure is required
5)
Higher ambient temperatures up to 60°C allowed with current derating at 40°C, in the range 40…50°C with 1.5% per 1K
and in the range 50…60°C with 1.9% per 1K
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......