Technical data
6.5 400 V converters
Power Module PM240-2
88
Hardware Installation Manual, 01/2020, A5E33294624B AL
6.5.1
General data, 400 V converters
Property
Version
Line voltage
FSA … FSC 380 V … 480 V 3 AC ± 10%
FSD … FSG 380 V … 480 V 3 AC ± 10% (in operation -20% < 1 min)
Line supply configurations Grounded TN/TT line supplies or non-grounded IT line supplies
Permissible line supplies (Page 46)
Line impedance
FSA … FSC 1%
≤
Uk < 4%, for values smaller than 1%, we recommend a line reactor, or
a Power Module with the next higher power rating.
FSD … FSG No restrictions
Power factor
λ
FSA … FSC
FSD … FSG
0.7 without line reactor for Uk
≥
1%
0.85 with line reactor for Uk < 1%
> 0.9
Output voltage
0 V 3 AC … 0.95 x input voltage (max.)
Input frequency
50 Hz … 60 Hz, ± 3 Hz
Output frequency
0 … 550 Hz, depending on the control mode
Inrush current
< LO base load input current
Overvoltage category ac-
cording to EN 61800-5-1
III for line supplies
Pulse frequency
Factory setting
•
4 kHz for devices with an LO base load power < 110 kW
•
2 kHz for devices with an LO base load power
≥
110 kW
Can be adjusted in 2 kHz steps as follows:
•
2 kHz … 16 kHz for devices with an LO base load power < 55 kW
•
2 kHz … 8 kHz for devices with an LO base load output of 55 kW … 250 kW
If you increase the pulse frequency, the converter reduces the maximum output current.
Current reduction as a function of the pulse frequency (Page 98)
Short-circuit current
(SCCR) and branch protec-
tion
Maximum permissible line short-circuit current
≤
100 kA rms
Branch protection and short-circuit strength according to UL and IEC
https://support.industry.siemens.com/cs/ww/en/view/109479152
Braking methods
DC braking, compound braking, dynamic braking with integrated braking chopper
Degree of protection ac-
cording to EN 60529
IP20
IP55 PT devices outside the control cabinet
Protection class according
to EN 61800-5-1
The converters are devices with protection class I
Touch protection according
to EN 50274
DGUV regulation 3 when used for the intended purpose
Cooling in compliance with
EN 60146
Forced air cooling AF
Safety Integrated
See function manual "Safety Integrated"
"Safety Integrated" function manual
https://support.industry.siemens.com/cs/ww/en/view/109751320
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......