Fundamental safety instructions
1.1 General safety instructions
Power Module PM240-2
12
Hardware Installation Manual, 01/2020, A5E33294624B AL
WARNING
Active implant malfunctions due to electromagnetic fields
Inverters generate electromagnetic fields (EMF) in operation. Electromagnetic fields may
interfere with active implants, e.g. pacemakers. People with active implants in the
immediate vicinity of an inverter are at risk.
•
As the operator of an EMF-emitting installation, assess the individual risks of persons
with active implants.
•
Observe the data on EMF emission provided in the product documentation.
WARNING
Unexpected movement of machines caused by radio devices or mobile phones
Using radio devices or mobile telephones in the immediate vicinity of the components can
result in equipment malfunction. Malfunctions may impair the functional safety of machines
and can therefore put people in danger or lead to property damage.
•
Therefore, if you move closer than 20 cm to the components, be sure to switch off radio
devices or mobile telephones.
•
Use the "SIEMENS Industry Online Support app" only on equipment that has already
been switched off.
NOTICE
Damage to motor insulation due to excessive voltages
When operated on systems with grounded line conductor or in the event of a ground fault in
the IT system, the motor insulation can be damaged by the higher voltage to ground. If you
use motors that have insulation that is not designed for operation with grounded line
conductors, you must perform the following measures:
•
IT system: Use a ground fault monitor and eliminate the fault as quickly as possible.
•
TN or TT systems with grounded line conductor: Use an isolating transformer on the line
side.
WARNING
Fire due to inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating of components with subsequent
fire and smoke. This can cause severe injury or even death. This can also result in
increased downtime and reduced service lives for devices/systems.
•
Ensure compliance with the specified minimum clearance as ventilation clearance for
the respective component.
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......