Installing
3.2 EMC-compliant installation of a machine or system
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
25
3.2.2
Cables
Cables with a high level of interference and cables with a low level of interference are
connected to the converter:
●
Cables with a high level of interference:
–
Cable between the line filter and converter
–
Motor cable
–
Cable at the converter DC link connection
–
Cable between the converter and braking resistor
●
Cables with a low level of interference:
–
Cable between the line and line filter
–
Signal and data cables
Cable routing inside the cabinet
●
Route the power cables with a high level of interference so that there is a minimum
clearance of 25 cm to cables with a low level of interference.
If the minimum clearance of 25 cm is not possible, insert separating metal sheets
between the cables with a high level of interference and cables with a low level of
interference. Connect these separating metal sheets to the mounting plate to establish a
good electrical connection.
●
Cables with a high level of interference and cables with a low level of interference may
only cross over at right angles:
●
Keep all of the cables as short as possible.
●
Route all of the cables close to the mounting plates or cabinet frames.
●
Route signal and data cables - as well as the associated equipotential bonding cables -
parallel and close to one another.
●
Twist incoming and outgoing unshielded individual conductors.
Alternatively, you can route incoming and outgoing conductors in parallel, but close to
one another.
●
Ground any unused conductors of signal and data cables at both ends.
●
Signal and data cables must only enter the cabinet from one side, e.g. from below.
●
Use shielded cables for the following connections:
–
Cable between the converter and line filter
–
Cable between the converter and output reactor or sine-wave filter
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......