Technical data
6.4 200 V converters
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
81
Table 6- 4
PM240-2, PT, frame size B, 200 V … 240 V 1 AC / 3 AC
Article No. without filter
Article No. with filter
6SL3211-1PB21-0UL0
6SL3211-1PB21-0AL0
LO base load power
2.2 kW
1 AC LO base load input current
24.0 A
3 AC LO base load input current
13.6 A
LO base load output current
10.4 A
HO base load power
1.5 kW
1 AC HO base load input current
20.9 A
3 AC HO base load input current
9.7 A
HO base load output current
7.4 A
Fuse according to IEC
Fuse according to UL, class J
3NA3812 (32 A)
35 A
Power loss
0.12 kW
1)
Required cooling air flow
9.2 l/s
Weight without filter
3.4 kg
Weight with filter
3.7 kg
1)
approx. 0.08 kW through the heat sink
Table 6- 5
PM240-2, IP 20, frame size C, 200 V … 240 V 1 AC / 3 AC
Article No. without filter
Article No. with filter
6SL3210-1PB21-4UL0
6SL3210-1PB21-4AL0
6SL3210-1PB21-8UL0
6SL3210-1PB21-8AL0
LO base load power
3 kW
4 kW
1 AC LO base load input current
35.9 A
43.0 A
3 AC LO base load input current
17.7 A
22.8 A
LO base load output current
13.6 A
17.5 A
HO base load power
2.2 kW
3 kW
1 AC HO base load input current
31.3 A
37.5 A
3 AC HO base load input current
13.6 A
17.7 A
HO base load output current
10.4 A
13.6 A
Fuse according to IEC
Fuse according to UL, class J
3NA3820 (50 A)
50 A
3NA3820 (50 A)
50 A
Power loss
0.14 kW
0.18 kW
Required cooling air flow
18.5 l/s
18.5 l/s
Weight without filter
5.0 kg
5.0 kg
Weight with filter
5.2 kg
5.2 kg
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......