Accessories
8.6 Line harmonics filter
Power Module PM240-2
126
Hardware Installation Manual, 01/2020, A5E33294624B AL
Table 8- 2
Assignment table
Power Module, 400 V
Line filter (Class B regarding conducted emissions)
Frame size
Article number
Power
Article number
FSA
6SL3210-1PE11-8UL1
6SL3210-1PE12-3UL1
6SL3210-1PE13-2UL1
6SL3210-1PE14-3UL1
6SL3210-1PE16-1UL1
6SL321 .-1PE18-0UL1
0.55
0.75
1.1
1.5
2.2
3.0
6SL3203-0BE17-7BA0
FSB
6SL3210-1PE21-1UL0
6SL3210-1PE21-4UL0
6SL321 .-1PE21-8UL0
4.0
5.5
7.5
6SL3203-0BE21-8BA0
FSC
6SL3210-1PE22-7UL0
6SL321 .-1PE23-3UL0
11
15
6SL3203-0BE23-8BA0
8.6
Line harmonics filter
The line harmonics filters reshape the distorted current back to the desired sinusoidal
waveform.
With the line harmonics filters the converter fulfills the IEEE 519 standards.
For technical details refer to the following link:
Line harmonics filters
https://www.schaffner.com/products/download/product/datasheet/fn-3440-ecosine-50hz-
Note
If you use a line harmonics filter the permissible line voltage is 380 V ... 415 V 3 AC ±10 %
instead of 380 V ... 480 V 3 AC ± 10 % without a line harmonics filter.
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......