Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
19
Installing
3
3.1
Installation conditions
General installation conditions
When installing the Power Modules carefully observe the conditions listed below in order to
guarantee reliable, continuous and disturbance-free operation.
●
The Power Modules are designed for installation in a control cabinet.
●
The Power Modules are certified for use in environments with degree of pollution 2
without condensation; i.e. in environments where no conductive pollution/dirt occurs.
●
The built-in units fulfill IP20 degree of protection at delivery status with the maximum
cross section for the connected cables.
●
Fast temperature changes of the air drawn in (e.g. by using cooling units) are not
permitted due to the risk of condensation.
●
Condensation is not permissible when switching on.
●
You can find the permissible conductor cross-sections for the terminals in:
Connection terminals at the converter (Page 57)
●
The following section describes how you can install the Power Module in compliance with
EMC regulations:
EMC-compliant installation of a machine or system (Page 22)
●
Devices in push-through technology – PT devices
–
PT devices have IP20 degree of protection and at the rear of the control cabinet they
fulfil IP55.
–
PT devices, FSF: A pressure compensation valve is necessary for the cabinet in order
to prevent underpressure in the cabinet.
●
For a system configuration in conformance with IEC, use the fuse types approved for IEC,
specified in the Technical data, or the circuit breakers under the following Internet
address.
–
Fuse types: Technical data (Page 73)
–
Circuit breaker
https://support.industry.siemens.com/cs/ww/en/view/109486009
Summary of Contents for SINAMICS G120
Page 1: ...Power Module PM240 2 ...
Page 2: ......
Page 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Page 175: ......
Page 176: ......