Commissioning (software)
4.4 Additional information on configuring the SINAMICS Integrated
SIMOTION D410
Commissioning Manual, 02/2012
93
4.4.2
Using vector drives
Changes need to be made in HW Config when SINAMICS vector drives are used. This
means, for example, that the T
I
/T
O
time and the minimum DP cycle for drives in chassis
format depend on the type of device used.
Therefore, we recommend adopting the following procedure when using a vector drive with
the SIMOTION D410:
Procedure
1.
Open HW Config. By "double clicking" the SINAMICS Integrated, you can change the
properties of the DP slave in the "Isochronous Operation" tab.
2.
For T
I
= T
O
=, enter an integer multiple of the current controller cycle. For the current
controller cycle, use 375 µs for devices in chassis format and 500 µs for the PM340.
3.
For T
DP
, enter an integer multiple of the speed controller cycle. For a drive on the
SINAMICS Integrated, T
DP
must be >= T
O
in all cases.
4.
Enter T
MAPC
= T
DP
(exception: You are working with cycle reduction; i.e. servo cycle > DP
cycle).
5.
Use the "Target system" > "Load" > "Download project to target system" menu command
to download the parameterization to the SIMOTION D410.
6.
After the download has successfully completed, you should determine the current and
speed controller cycles of the drive from the drive's expert list, because the cycle clocks
are set in the SINAMICS drive unit after a project has been downloaded.
–
P0115[0] Current controller clock cycle
–
P0115[1] Speed controller clock cycle
7.
If the current and speed controller cycles from the expert list are different to the cycles
used in steps 2 and 3, you will have to repeat the steps using the most up-to-date values
for the current and speed controller cycles.
Table 4- 3
Vector drive
Example
Settings
Vector drive (chassis format)
Current controller cycle = 375 µs
Speed controller cycle = 1.5 ms
T
I
= T
O
= At least 375 µs
T
DP
= 1.5 ms (... or 3 ms, or 6 ms ....)
T
MAPC
= T
DP
For the SIMOTION D410, a minimum of 2 ms is recommended for
the servo cycle.
For this reason, set T
MAPC
= T
DP
= 3 ms or higher.
Vector drive (PM340)
Current controller cycle = 500 µs
Speed controller cycle = 2 ms
T
I
= T
O
= At least 500 µs
T
DP
= 2 ms (... or 4 ms, 8 ms, ....)
T
MAPC
= T
DP