Commissioning (software)
4.3 Performing an online configuration
SIMOTION D410
88
Commissioning Manual, 02/2012
6.
Click "Create" to start the automatic configuration.
The configuration data is uploaded (Load to PG) automatically as soon as automatic
configuration is completed.
Note
The components' firmware is automatically updated, depending on the FW version on the
CompactFlash Card and on the SINAMICS components.
The update procedure can take several minutes and is indicated in the "Automatic
Configuration" dialog box by the following message:
State of the drive unit: Automatic FW update of DRIVE-CLiQ components.
An FW update on the SIMOTION D410 is indicated by the RDY LED flashing yellow,
while on the DRIVE-CLiQ components (TM, SMC, etc.) it is indicated by the RDY LED
flashing red/green.
•
FW update running: RDY LED flashes slowly (0.5 Hz)
•
FW update complete: RDY LED flashes quickly (2 Hz)
Go offline once all the FW updates have been completed. then switch the 24 V supply for
the upgraded initialization components off/on.
7.
Execute the "Copy RAM to ROM ..." function on the D410 and SINAMICS Integrated.
This saves the project on the CompactFlash Card so that it does not need to be reloaded
after switching off and on.