6.5.4
Laying cables
● Lay the cables in accordance with IEC/EN 60364-5-52.
● For fixed cables, use EMC- and Ex-certified cable glands with strain relief. Screw the cable
glands into the threaded holes in the entry plate, which can be unscrewed. The cable glands
are not included in the scope of supply.
Comply with the installation and operation conditions specified in the certificate for these
cable glands and check that they have been fully complied with.
● For loose cables, use twist-protection cable glands with strain relief.
● Use shielded cables whose shields are conductively connected to a large area of the
terminal box of the motor via EMC cable glands.
● Arrange the exposed connecting cables in the terminal box so that the PE conductor has
excess length and the insulation of the cable strands cannot be damaged.
● In the case of aluminum connecting bars, insert a steel washer between the cable lug and
the connecting bar. This prevents contact corrosion.
● Correctly close and seal threads or holes that are not being used ensuring that the IP degree
of protection is maintained. The IP degree of protection is specified on the rating plate.
Replace the cable glands that are not being used by appropriately certified screw plugs.
6.5.5
Connecting cables with cable lugs
1. Select the cable lugs according to the required cable cross-section and fixing screw or stud
size. Information about the maximum cross-section for the respective standard terminal box
design can be found in the catalog.
A sloped/angular arrangement of the supply cables is only permitted provided the required
minimum air clearances are met.
2. Remove the insulation from the conductor ends so that the remaining insulation reaches
almost up to the cable lug
①
. Connect only one conductor per cable lug.
3. Fasten the cable lug to the end of the conductor correctly, e.g. by squeezing.
Figure 6-9
Connection with cable lug and fixing screw (schematic diagram)
4. Insulate the cable lug sleeves where necessary to ensure minimum air clearances and the
creepage distance are maintained.
Electrical connection
6.5 Inserting and routing the cables
SIMOTICS FD 1MM1
Operating Instructions 02/2019
85
Summary of Contents for SIMOTICS FD 1MM1 Series
Page 2: ...05 02 2019 16 03 V11 01 ...
Page 30: ...Description SIMOTICS FD 1MM1 30 Operating Instructions 02 2019 ...
Page 142: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MM1 142 Operating Instructions 02 2019 ...
Page 166: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MM1 166 Operating Instructions 02 2019 ...
Page 168: ...Service and Support SIMOTICS FD 1MM1 168 Operating Instructions 02 2019 ...
Page 172: ...Quality documents SIMOTICS FD 1MM1 172 Operating Instructions 02 2019 ...
Page 177: ......