7.7
Set values for monitoring the winding temperature
Prior to commissioning
Before running the machine for the first time, set the temperature value for shutdown on the
monitoring device.
Table 7-3
Set value for commissioning
Set value
Temperature
Alarm
145° C
Shutting down
155° C
Normal operation
1. Measure the normal operating temperature T
op
at the installation location in ° C.
2. Set the values for shutdown and warning corresponding to the operating temperature T
op
.
Table 7-4
Set values during normal operation
Set value
Temperature for insulation class 180(H), utilization 155(F)
Alarm
T
op
+ 10 K ≤ 145° C
Shutting down
T
op
+ 15 K ≤ 155° C
7.8
Test run
After installation or inspection, carry out a test run:
1. Start up the machine without a load. To do this, close the circuit breaker and do not switch
off prematurely. Check whether it is running smoothly.
Switching the machine off again while it is starting up and still running at slow speed should
be kept to a bare minimum, for example for checking the direction of rotation or for checking
in general.
Allow the machine to run down before switching it on again.
2. If the machine is running smoothly and evenly, switch on the cooling equipment. Continue
to observe the machine for a while in no-load operation.
Start-up
7.7 Set values for monitoring the winding temperature
SIMOTICS FD 1MM1
100
Operating Instructions 02/2019
Summary of Contents for SIMOTICS FD 1MM1 Series
Page 2: ...05 02 2019 16 03 V11 01 ...
Page 30: ...Description SIMOTICS FD 1MM1 30 Operating Instructions 02 2019 ...
Page 142: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MM1 142 Operating Instructions 02 2019 ...
Page 166: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MM1 166 Operating Instructions 02 2019 ...
Page 168: ...Service and Support SIMOTICS FD 1MM1 168 Operating Instructions 02 2019 ...
Page 172: ...Quality documents SIMOTICS FD 1MM1 172 Operating Instructions 02 2019 ...
Page 177: ......